Chicago Plant Status

String Timestamp Voltage
OK Chicago String A Sep 1, 2021, 5:00:00 PM 47.503 V
OK Chicago String B Sep 1, 2021, 5:00:00 PM 23.751 V
OK Chicago String C Sep 1, 2021, 5:00:00 PM 23.938 V
OK Chicago String D Sep 1, 2021, 5:00:00 PM 48.284 V

Battery Timestamp Voltage Temperature Conductance Strap Resistance T-Comp
Chicago String A
OK Battery 1 Sep 1, 2021, 5:00:00 PM 11.808 V 67 °F 494 S (1,000) 50 µΩ 96 %
OK Battery 2 Sep 1, 2021, 5:00:00 PM 11.867 V 68 °F 503 S (1,000) 50 µΩ 94 %
OK Battery 3 Sep 1, 2021, 5:00:00 PM 11.901 V 68 °F 505 S (1,000) 51 µΩ 94 %
OK Battery 4 Sep 1, 2021, 5:00:00 PM 11.927 V 67 °F 507 S (1,000) 51 µΩ 95 %
Chicago String B
OK Battery 1 Sep 1, 2021, 5:00:00 PM 11.774 V 68 °F 493 S (1,000) 50 µΩ 96 %
OK Battery 2 Sep 1, 2021, 5:00:00 PM 11.977 V 67 °F 508 S (1,000) 50 µΩ 93 %
Chicago String C
OK Battery 1 Sep 1, 2021, 5:00:00 PM 12.038 V 68 °F 495 S (1,000) 50 µΩ 94 %
OK Battery 2 Sep 1, 2021, 5:00:00 PM 11.900 V 68 °F 499 S (1,000) 50 µΩ 94 %
Chicago String D
OK Battery 1 Sep 1, 2021, 5:00:00 PM 11.992 V 68 °F 494 S (1,000) 49 µΩ 95 %
OK Battery 2 Sep 1, 2021, 5:00:00 PM 12.223 V 68 °F 509 S (1,000) 49 µΩ 96 %
OK Battery 3 Sep 1, 2021, 5:00:00 PM 11.851 V 68 °F 504 S (1,000) 50 µΩ 96 %
OK Battery 4 Sep 1, 2021, 5:00:00 PM 12.217 V 68 °F 494 S (1,000) 50 µΩ 95 %